- altitude above sea level not more 1000 m;
- thickness of the crust of ice less than 20 mm;
- wind speed in glaze condition to 15 m/s;
- wind speed in the absence of glaze to 40 m/s;
- environment value of temperature of air + 40 °C;
- environment value of temperature of air - 60°C.
Environment not explosive, the content of corrosion-active agents must comply with the atmosphere requirements I and II according to GOST 15150-69.
Decoding of bus-bar symbols:
AIZ-X1-X2X3-X4-UHL1,
AIZ- trade mark of bus-bar supports,
X1- nominal voltage in kV,
X2- index, which shows standard performance of bus-bar support (Z- rigid fitting of aluminium tubular bus-bar)
X3-conditional diameter of aluminium bus,
X4- pollution degree by GOST9920,
UHL- pollution performance by GOST 15150, installation category by GOST15150.
Variants of performance are introduced in table 1.
Type of busbar support of rigid bus-bar |
Darwing.№ |
Diameter of aluminium tube of rigid bus-bar, mm |
Conventional diameter of bus |
Spacing, H, mm |
Weight, kg |
AIZ-10-Z30-4 UHL1 |
2 |
30/25 |
30 |
359 |
12,8 |
AIZ-10-Z40-4 UHL1 |
2 |
40/35 |
40 |
359 |
12,9 |
AIZ-10-Z50-4 УХЛ1 |
2 |
50/45 |
50 |
360 |
13,2 |
AIZ-10-Z70-4 УХЛ1 |
2 |
70/64 |
70 |
370 |
13,5 |
AIZ-10-Z80-4 УХЛ1 |
2 |
80/72 |
80 |
378 |
14,7 |
AIZ-10-Z90-4 УХЛ1 |
2 |
90/80 |
90 |
382 |
15,0 |
AIZ-10-Z100-4 УХЛ1 |
2 |
100/90 |
100 |
394 |
15,2 |
AIZ-10-Z110-4 УХЛ1 |
1 |
110/100 |
110 |
400 |
15,5 |
AIZ-10-Z120-4 УХЛ1 |
1 |
120/110 |
120 |
402 |
16,0 |
AIZ-10-Z130-4 УХЛ1 |
1 |
130/116 |
130 |
415 |
18,0 |
AIZ-10-Z140-4 УХЛ1 |
1 |
140/120 |
140 |
420 |
18,0 |
AIZ-10-Z150-4 УХЛ1 |
1 |
150/136 |
150 |
430 |
19,1 |
AIZ-10-Z170-4 УХЛ1 |
1 |
170/156 |
170 |
450 |
20,2 |
AIZ-10-Z200-4 УХЛ1 |
1 |
200/180 |
200 |
470 |
24,3 |
AIZ-10-Z250-4 УХЛ1 |
1 |
250/230 |
250 |
495 |
30,2 |
Main technical characteristics
Technical specifications |
Value |
Rated voltage, kV |
10 |
Maximal working voltage, kV |
12 |
Test voltage of full lightning impulse, kV |
75 |
50%-ing discharge voltage of industrial frequency in polluted and humid condition, kV
-when the specific surface conductivity of the layer of pollution, mkSm |
13 |
Minimal breaking load on bend, kN, not less |
10 |
The minimal breaking torque, not less, kN*m |
2 |
Creepage distance, cm |
30 |
The highest peak of the rated short time withstand current (current of electrodynamic resistance), kA |
31,5 |
Acceptable traction of buses in the horizontal plane of bus-bar supports in the place of bus fixation, N |
1480 |
Dimensions of bottom flange, mm |
Diam. 127* 4hols.diam.13 |