AIZ-10-D
Polymer bus-bar supports for movable fixation of aluminium tube of rigid bus-bar for the 10 kV voltage
The bus- bar supports of outdoor application AIZ-10-D are used for movable fixationof aluminium tubular buses of rigid bus- bars at 10 kV voltage and current frequency to 60 Hz in open distribution devices of electric power stations and substations.
Bus-bar supports are made in climatic design UHL, category 1 according to GOST 15543.1-89 and GOST 15150-69, in which:
- altitude above sea level not more 1000 m;
- thickness of the crust of ice less than 20 mm;
- wind speed in glaze condition to 15 m/s;
- wind speed in the absence of glaze to 40 m/s;
- environment value of temperature of air + 40 °C;
- environment value of temperature of air - 60°C.
Environment not explosive, the content of corrosion-active agents must comply with the atmosphere requirements I and II according to GOST 15150-69.
Decoding of bus-bar symbols:
AIZ-X1-X2X3-X4-UHL1,
AIZ- trade mark of bus-bar supports,
X1- nominal voltage in kV,
X2- index, which shows standard performance of bus-bar support (D- movable fixation platform of aluminium tubular bus),
X3- conditional diameter of aluminium bus,
X4- pollution degree by GOST9920, UHL- pollution performance by GOST 15150, installation category by GOST15150.
![]() |
|
Variants of performance are introduced in table 1.
|
Type of bus-bar support of rigid bus-bar |
Diameter of aluminium tube of rigid bus-bar, mm |
Conventional diameter of bus |
Spacing, H, mm |
Weight, kg |
|
AIZ-10-D50-4 UHL1 |
50/45 |
50 |
370 |
15,0 |
|
AIZ-10-D60-4 UHL1 |
60/54 |
60 |
380 |
15,0 |
|
AIZ-10-D70-4 UHL1 |
70/64 |
70 |
405 |
15,5 |
|
AIZ-10-D80-4 UHL1 |
80/72 |
80 |
410 |
16,0 |
|
AIZ-10-D90-4 UHL1 |
90/80 |
90 |
410 |
16,4 |
|
AIZ-10-D100-4 UHL1 |
100/90 |
100 |
415 |
17,0 |
|
AIZ-10-D110-4 UHL1 |
110/100 |
110 |
425 |
17,5 |
|
AIZ-10-D120-4 UHL1 |
120/110 |
120 |
425 |
17,5 |
|
AIZ-10-D130-4 UHL1 |
130/116 |
130 |
435 |
18,0 |
|
AIZ-10-D140-4 UHL1 |
140/120 |
140 |
440 |
18,5 |
|
AIZ-10-D150-4 UHL1 |
150/136 |
150 |
440 |
18,7 |
|
AIZ-10-D170-4 UHL1 |
170/156 |
170 |
460 |
20,5 |
|
AIZ-10-D200-4 UHL1 |
200/180 |
200 |
470 |
22,2 |
|
AIZ-10-D250-4 UHL1 |
250/230 |
250 |
495 |
23,9 |
Main technical characteristics
|
Technical specifications |
Value |
|
Rated voltage, kV |
10 |
|
Maximal working voltage, kV |
12 |
|
Test voltage of full lightning impulse, kV |
75 |
|
50%-ing discharge voltage of industrial frequency in polluted and humid condition, kV
-when the specific surface conductivity of the layer of pollution, mkSm |
13 |
|
Minimal breaking load on bend, kN, not less |
10 |
|
The minimal breaking torque, not less, kN*m |
2 |
|
Creepage distance, cm |
30 |
|
The highest peak of the rated short time withstand current (current of electrodynamic resistance), kA |
31,5 |
|
Acceptable traction of buses in the horizontal plane of bus-bar supports in the place of bus fixation, N |
1480 |
|
Dimensions of bottom flange, mm |
Diam. 127* 4hols.diam.13 |