Ballast BL, 2BL, 3BL, 4BL, BP
Ballast to supporting clamps BL
NOMINATION:
To prevent pulling up the insulating suspension or too much of its deviation from the vertical under the influence of wind.
Ballast meet TU 34 13.10519-88.
|
|
Designation |
Dimensions, mm |
Weight controlling level, kg |
To clamps of type |
Weight, kg |
||
A |
B |
L |
||||
BL-100-1 |
400 |
310 |
320 |
100 50 |
PG-1-11, PGN-1-5, PN-2-6, PGN-3-5 |
103 |
BL-200-1 |
480 |
200 150 100 50 |
205 |
|||
BL-400-1 |
425 |
395 |
732 |
400 300 200 100 |
PGN-1-5, PGN-2-6, PGN-3-5 |
411,5 |
BL-400-5 |
400 |
PGN-5-3 |
415 |
_________________________________________________________________________________________________________________
Ballast to supporting clamps for one wire
NOMINATION:
Type |
Dimensions, mm |
Weight controlling level, kg
|
To clamps of type |
Weight, kg |
||
A |
B |
L |
||||
2BL-800-3 |
540 |
485 |
858 |
800 to 400, through 100 kg |
2PGN-5-7 |
815 |
3BL-1400-1 |
|
1322 |
1400 to 800, through 100 kg |
2PGN-5-7, 3PGN-5-7 |
1422 |
|
3BL-1400-4 |
|
1715 |
1400 to 100, through 100 kg |
3PGN2-5-4 |
1430 |
|
4BL-1000-1 |
- |
- |
1690 |
1000 to 100, through 100 kg |
4PGN2-5-2А |
1030 |
_________________________________________________________________________________________________________________
Ballast type BP
NOMINATION:
To prevent pulling up the insulating suspension or too much of its deviation from the vertical under the influence of wind. Ballast meet TU 34 13.10519-88.
|
|
Designation |
Wire diameter, mm |
L, mm |
Weight, kg |
BP-50-1 |
7,5-11,5 |
176 |
51 |
BP-1-100-1 |
13,0-17,1 |
302 |
102 |
BP-2-100-1 |
18,2-24,5 |
||
BP-3-100-1 |
25,5-30,6 |