Bus-bar supports for end fixation of aluminium tube of rigid bus-bar .. Product #: based on 0 Reviews Regular price: $0.00 $0.00

AIZ-35-K

 

The bus- bar supports of outdoor application AIZ-35-K are used for aluminium tubes supporting of rigid bus- bars at 35 kV voltage and current frequency to 60 Hz in open distribution devices of electric power stations and substations.

1.1.2 Bus-bar supports are made in climatic design UHL, category 1 according to GOST 15543.1-89 and GOST 15150-69, in which:

 

  • altitude above sea level not more 1000 m;
  • thickness of the crust of ice less than 20 mm;
  • wind speed in glaze condition to 15 m/s;
  • wind speed in the absence of glaze to 40 m/s;
  • environment value of temperature of air + 40 °C;
  • environment value of temperature of air - 60°C.

 

Environment not explosive, the content of corrosion-active agents must comply with the atmosphere requirements

I and II according to GOST 15150-69.

 

Decoding of bus-bar symbols:

AIZ-X1-X2X3-X4-UHL1,

 

AIZ- trade mark of bus-bar supports,

X1- nominal voltage in kV,

X2- index, which shows standard performance of bus-bar support (K- end fixation of aluminium tube),

X3- conditional diameter of aluminium bus,

X4- pollution degree by GOST9920,

UHL- pollution performance by GOST 15150, installation category by GOST15150.

 

 

Variants of performance are introduced

Type of bus-bar support of rigid bus-bar

Diameter of tube of rigid bus-bar, mm

Conventional diameter of tubular bus

Spacing, H, mm

Weight, kg

AIZ-35-К50-4 UHL1

50/45

50

495

15,0

AIZ-35-К60-4 UHL1

60/54

60

498

15,0

AIZ-35-К70-4 UHL1

70/64

70

525

15,1

AIZ-35-К80-4 UHL1

80/72

80

530

15,2

AIZ-35-К90-4 UHL1

90/80

90

530

15,4

AIZ-35-К100-4 UHL1

100/90

100

545

15,7

AIZ-35-К110-4 UHL1

110/100

110

545

17,5

AIZ-35-К120-4 UHL1

120/110

120

550

17,8

AIZ-35-К130-4 UHL1

130/116

130

560

17,9

AIZ-35-К140-4 UHL1

140/120

140

570

18,0

AIZ-35-К150-4 UHL1

150/136

150

600

18,3

AIZ-35-К170-4 UHL1

170/156

170

620

18,5

AIZ-35-К200-4 UHL1

200/180

200

650

18,7

AIZ-35-К250-4 UHL1

250/230

250

655

18,9

 

 

 

Main technical characteristics

 

Technical specifications

Value

Rated voltage, kV

35

Maximal working voltage, kV

40,5

Test voltage of full lightning impulse, kV

190

50%-ing discharge voltage of industrial frequency in polluted and humid condition, kV

 

-when the specific surface conductivity of the layer of pollution, mkSm

42


20

Minimal breaking load on bend, kN, not less

10

The minimal breaking torque, not less, kN*m

1

Creepage distance, cm

95

The highest peak of the rated short time withstand current (current of electrodynamic resistance), kA

31,5

Acceptable traction of buses in the horizontal plane of bus-bar supports in the place of  bus fixation,  N

1480

Dimensions of bottom flange, mm

Diam. 127* 4hols.diam.13

 

 

Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-0 ,,Bus-bar supports for the 10-220 kV voltage”.

The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia.

 

Advantages of bus-bar supports AIZ-35-K....UHL1

 

Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalism; ensures safety conditions even during installation and exploitation works.

The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That’s why it eliminates possibility of personal injury.